Application is measuring chilled water at low flow rates; configured as a BTU meter. Good test of accuracy at low end of rotor range; confidence in readings based on historical records. Typical frequency 55.98 Hz, velocity 3.0 ft/sec. Reading 20°F difference between T1 and T2 (placed at supply and return). BTU signal interfacing to Building Automation System (BAS) via 4–20 mA presently; Ethernet trials under